  1. HHPA

    HHPA

    On page 7 of the manual for the
    110/60/ATS-3/B diagram, contact GTS/Aux should be in the open position? This diagram shows that the generator is active and the line is inactive without the mode switch being set to automatic. When the generator kicks on contactor GTS becomes energized thus opening contact GTS/AUX assuming the mode is automatic?

    John

    Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal

    Something wrong with this post? Thanks for letting us know. If you can point us in the right direction...

    • Dale Riebel

      Admin Dale Riebel

      John, the wiring diagram is drawn representing no voltage applied. Once voltage is applied the contacts represented in the drawing change from open to closed and vice versa. You can call our Service Department @ 507-357-6831 to discuss the drawing further if you wish.

      Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal

      Something wrong with this post? Thanks for letting us know. If you can point us in the right direction...

  2. Question

    ken corey

    the relay doesn’t do anything in any position

    Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal

    Something wrong with this post? Thanks for letting us know. If you can point us in the right direction...

×